| Rated insulation voltage | Voltage type |
|---|---|
| Ui = 1000 V | a.c. |
II
In = 63 A
| power dissipation capability Pde | Temperature difference |
|---|---|
| Pde = 26 W | 30 K |
| Number of cable entries | Type of cable entry | Size of the metric knockouts | Position of cable entry |
|---|---|---|---|
| 4 | metric knockouts | M20 | wall top+bottom |
| 2 | metric knockouts | M20, M25 | wall top+bottom |
| 1 | metric knockouts | M32 | wall top+bottom |
Door
Yes
12 modules
1
sealing plug, DIN rail(s), blanking strips, labelling strips, cable entry cover
IP65
Open
Indoor installation
35 °C
-5 °C up to +40 °C
≤ 50 % at 40 °C, ≤ 100 % at 25 °C
Polystyrene
750 °C
V-2
-25 °C up to +80 °C
Yes
Yes
333 mm
295 mm
129 mm
1.786 kg
EN 60670-1, DIN EN 60670-24
6100647
4012591616481
1
85381000
DYNAMIC: EC000214 - Small distribution board
ETIM-8.0: EC000214 - Small distribution board
ETIM-7.0: EC000214 - Small distribution board
ETIM-6.0: EC000214 - Small distribution board
ETIM-5.0: EC000214 - Small distribution board
ETIM-4.0: EC000214 - Small distribution board
Small-type distribution boards in accordance with DIN EN 60670-24 and IEC 61439-3, for installation of devices with snap-on mounting up to 63 A to DIN 43880, double insulated (protection class II). Suitable for indoor areas and protected outdoor installation according to DIN VDE 0100, Part 737. For ambient temperature maximum +40 °C and minimum -5 °C, at relative humidity 50% at +40 °C or 100% at +25 °C. Material temperature resistance from -25 °C to +70 °C. Flammability in accordance with VDE 0471, Part 2 – glow-wire test 750 °C, UL Subject 94 V-2. Rated voltage 400 V. Material: thermoplastic, halogen- and silicone-free. Color: grey, RAL 7035, with transparent door across all installation rows. Manufacturer: HENSEL KV.
Degree of protection: IP 65 with metric knockouts. 12 modules of 18 mm each. Dimensions HxWxD 333 x 295 x 129 mm.