FP 4212

  • Fuse box with fuse switch disconnector
  • 2x Fuse switch disconnector NH000, 3-pole
Product properties
Downloads
Digital product data
Product properties

ELECTRICAL PROPERTIES

Rated voltage:

Un = 690 V

Rated insulation voltage:
Rated insulation voltageVoltage type
Ui = 690 Va.c.
Ui = 1000 Vd.c.
Protection class:

withoutin orer to achieve protection class II and protection class IP 65: please order closing plate set, single closing plate sets and flanges separately.

Rated current (of the device):

In = 125 A

Rated current of a circuit:

InC = 100 Afor design verification of permissible temperature rise in accordance with IEC 61439-1, section 10.10.4

Rated conditional short-circuit current:

Icc = 50 kA

CONNECTION DATA

Connection type:

Screw connection

Connection cross-section device (outgoing):
Maximum number of conductors clamping units eachConductor cross-section min.Conductor cross-section max.Conductor cross sectionConductor typeConductor material
12.5 mm²50 mm²flexible
11.5 mm²10 mm²solidround
116 mm²50 mm²strandedround
Connection cross-section N/PE terminal to device:
Maximum number of conductors clamping units eachConductor cross-section min.Conductor cross-section max.Conductor cross sectionConductor typeConductor material
12.5 mm²35 mm²flexible with end ferruleCu
12.5 mm²50 mm²solid, strandedCu
16 mm²50 mm²solid, strandedAl
125 mm²35 mm²flexibleCu
Connection flat device:
WidthDepth / ThicknessConductor material
9 mm10 mmCu
Connection type:
Type of cableConnection typeConnection size
terminal
Wiring area changeable:

Yes

MECHANICAL PROPERTIES

With additional protection cover behind the lid
Type of lid fastening:

Tool operation

Delivered accessories:

connector

Can be combined:

Yes

IP degree of protection:

in connection with accessories

Impact strength:

IK08

Sealable without accessories:

No

AMBIENT CONDITIONS

Application area:

Indoor installation

Maximum ambient temperature 24 h:

35 °C

Ambient temperature:

-5 °C up to +40 °C

Relative humidity:

≤ 50 % at 40 °C, ≤ 100 % at 25 °C

Rated loading factors

Rated power dissipation in ENYGUIDE:
power dissipation capability PdeTemperature difference
Pde = 0.6 W1 K
Power dissipation of the device per pole:
Pv = 1.7 W

MATERIAL PROPERTIES

Material:

Polycarbonate

Glow wire test according to IEC 60695-2-11:

960 °C

UV resistant according to DIN EN IEC 61439-1:

Yes

Halogen-free:

Yes

Silicone-free:

Yes

DIMENSIONS

Height:

360 mm

Width:

270 mm

Depth:

163 mm

Net weight:

4.415 kg

COLOURS

Colour of the lid:

transparent

Bottom part colour:

grey

CERTIFICATES

Conforming to the standards:

DIN EN IEC 61439-3

SALES DATA

Product number:

68000230

EAN:

4012591105480

Pack unit:

1

Customs tariff number:

85371098

ETIM class:

DYNAMIC: EC000249 - Fuse switch disconnector with housing
ETIM-9.0: EC000249 - Fuse switch disconnector with housing
ETIM-8.0: EC000249 - Fuse switch disconnector with housing
ETIM-7.0: EC000249 - Fuse switch disconnector with housing
ETIM-6.0: EC000249 - Fuse switch disconnector with housing
ETIM-5.0: EC000249 - Fuse switch disconnector with housing
ETIM-4.0: EC000249 - Fuse switch disconnector with housing

NOTE

Before connecting, aluminum conductors must be pre-treated according to the appropriate technical recommendations, see technical information aluminum conductors
Note on the product:
  • with connection for splitting-up incoming cable
  • with connectors for connecting two boxes

TENDER TEXT

Tender text (system):

Combinable enclosure system with door for the assembly of distribution boards up to 250 A to be opperated by ordinary persons (DBO) in accordance with IEC 61439-3 for surface-mounting. Enclosures are suitable for the outdoor installation - harsh environment and / or outdoor, however the climatic influences and effects on the equipment are to be considered. Bottom parts and doors are made from impact-resistant polycarbonate, halogen- and silicone-free, colour RAL 7035. All enclosures with doors, which are lockable and sealable. Operation of device behind the doors. Burning behavior in accordance with IEC 60695-2-11 Glow wire test + 960° C. Protective measure: protective insulation (protection class II). Make: Hensel ENYSTAR.

Tender text (product):

HRC fuse box with fuse switch disconnector NH 00C, 3-pole, with PE and N terminals. Door lock with tool operation. Degree of protection: IP 65 according to IEC 60 529. Dimensions HxWxD 360 x 270 x 163 mm

Downloads
Digital product data

Attached accessories

ACCESSORIES

We use cookies

In order to optimally design our website for you and to continuously improve it, we use cookies and external components. You can choose which services you want to allow. Further informations are available in our Privacy Policy