Un = 690 V
| Rated insulation voltage | Voltage type |
|---|---|
| Ui = 690 V | a.c. |
| Ui = 1000 V | d.c. |
II
In = 250 A
InC = 200 Afor design verification of permissible temperature rise in accordance with IEC 61439-1, section 10.10.4
| Rated ultimate short-circuit breaking capacity | Rated voltage | Voltage type |
|---|---|---|
| ICS = ICU = 8 kA | Un = 690 V | a.c. |
| ICS = ICU = 36 kA | Un = 415 V | a.c. |
175 A - 250 A
1
| Maximum number of conductors clamping units each | Conductor cross-section min. | Conductor cross-section max. | Conductor cross section | Conductor type | Conductor material |
|---|---|---|---|---|---|
| 1 | 120 mm² | 185 mm² | round | Cu, Al |
| Maximum number of conductors clamping units each | Conductor cross-section min. | Conductor cross-section max. | Conductor cross section | Conductor type | Conductor material |
|---|---|---|---|---|---|
| 1 | 70 mm² | 240 mm² | stranded | round | Cu, Al |
| 1 | 120 mm² | 240 mm² | solid | sector | Cu, Al |
| 1 | 95 mm² | 240 mm² | stranded | sector | Cu, Al |
| Width | Depth / Thickness | Conductor material |
|---|---|---|
| 25 mm | 5 mm | Cu |
Tool operation
Yes
IP65
IK08
Indoor installation
35 °C
-5 °C up to +40 °C
≤ 50 % at 40 °C, ≤ 100 % at 25 °C
| power dissipation capability Pde | Temperature difference |
|---|---|
| Pde = 2 W | 1 K |
Polycarbonate
960 °C
Yes
Yes
Yes
600 mm
300 mm
262 mm
8.321 kg
transparent
grey
DIN EN IEC 61439-2
20001187
4012591115366
1
85371098
DYNAMIC: EC002283 - Distributor assembly with power circuit-breaker
ETIM-8.0: EC002283 - Distributor assembly with power circuit-breaker
ETIM-7.0: EC002283 - Distributor assembly with power circuit-breaker
ETIM-6.0: EC002283 - Distributor assembly with power circuit-breaker
ETIM-5.0: EC002283 - Distributor assembly with power circuit-breaker
ETIM-4.0: EC002283 - Distributor assembly with power circuit-breaker
Insulation-enclosed power distribution board as power switchgear and controlgear assembly (PSC) in accordance with IEC 61439-2 for wall mounting. The enclosures must be suitable for outdoor installation - harsh environment and/or outdoor installation - the climatic effects on the equipment must be considered. Bottom parts and lids of the boxes made from impact-resistant polycarbonate, halogen and silicone-free, colour RAL 7035, transparent lid with quick action fasteners for tool operation. Burning behaviour according to IEC 60695-2-11 glow wire test + 960°C. Maximum water absorption 10 mg in accordance with DIN 53473. Protective measure: totally insulated (protection class II), Make: HENSEL Mi Power distribution board.
Circuit breaker box, 3-pole, with overload and short circuit release, with PE and N terminals. Degree of protection: IP 65 according to IEC 60 529. Dimensions HxWxD 600 x 300 x 262 mm