Ui = 400 V
In = 57 A
E30, E60, E90
Dätwyler, Eupen
PH120insulation integrity in accordance with BS EN 50200 in connection with insulation retaining cables
| Maximum number of conductors clamping units each | Conductor cross-section min. | Conductor cross-section max. | Conductor cross section | Conductor type | Conductor material |
|---|---|---|---|---|---|
| 4 | 1.5 mm² | 1.5 mm² | solid, stranded, flexible | round | Cu |
| 2 | 2.5 mm² | 2.5 mm² | solid, stranded, flexible | round | Cu |
| 1 | 4 mm² | 6 mm² | solid, stranded, flexible | round | Cu |
| 1 | 10 mm² | 10 mm² | solid | round | Cu |
2
Screw connection
No
7 mm
1.2 Nm
| Number of cable entries | Type of cable entry | Size of the metric knockouts | Position of cable entry |
|---|---|---|---|
| 7 | metric knockouts | M20, M25 | wall |
Quick locking: opening and closing by quarter turn, locked position well visible (open - locked)
screw anchor
IP66IP degree of protection of the included Grommets 3x EDKF 25: IP65, sealing range 9 mm - 17 mm
IK09
Yes
Concrete C20/C25, Solid lime sandstone KSV 12, Brick MZ 12, Clinker KS 12
Indoor installation
35 °C
-25 °C up to +40 °C
≤ 50 % at 40 °C, ≤ 100 % at 25 °C
Polycarbonate
Yes
Yes
104 mm
104 mm
70 mm
0.418 kg
DIN EN 60670-1/-22, IEC 60670-1/-22, DIN 4102-12
| Type of certificate | Certificate number |
|---|---|
| AbP | P-MPA-E-15-018 |
62000181
4012591126034
1
85369010
DYNAMIC: EC002600 - Box/housing for surface mounting on the wall/ceiling
ETIM-8.0: EC002600 - Box/housing for surface mounting on the wall/ceiling
ETIM-7.0: EC002600 - Box/housing for surface mounting on the wall/ceiling
ETIM-6.0: EC002600 - Box/housing for surface mounting on the wall/ceiling
ETIM-5.0: EC002600 - Box/housing for surface mounting on the wall/ceiling
ETIM-4.0: EC002600 - Box/housing for surface mounting on the wall/ceiling
Cable junction boxes in accordance with IEC 60670-22 with built-in connecting terminal, 5-pole. Tested for intrinsic fire resistance according to DIN 4102 part 12 together with function-retaining cables of the manufacturers: Dätwyler and Eupen according to the test certificates of cable manufacturers. Functional integrity 30 minutes, classification E 30 or 90 minutes, classification E 90. Installation with fire protection-approved fasteners included in delivery. Tested for insulation integrity PH120 according to BS EN 50200 in conjunction with insulation-preserving cables, see test certificate, download at www.hensel.electric.de Type – Documents.Suitable for indoor installation (normal environment and/or protected outdoor) according to DIN VDE 0100, part 737. Degree of protection according to IEC 60529: IP 66 with cable glands. Rated insulation voltage: 400 V. Material: Thermoplastic, halogen- and silicone-free. Colour: RAL 2003, orange. Cover fastening with quick-release fastener, can be sealed without accessories. Manufacturer: HENSEL FK.
Rated cross-section: branch 1.5-2.5 mm² and connect 1.5-4 mm², dimensions HxWxD 104 x 104 x 70 mm