Ui = 400 V
E30, E60, E90
Dätwyler, Eupen
PH120insulation integrity in accordance with BS EN 50200 in connection with insulation retaining cables
Screw connection
| Type of terminal | Maximum number of conductors clamping units each | Conductor cross-section min. | Conductor cross-section max. | Conductor material | Dismantling length | Tightening torque of the terminal |
|---|---|---|---|---|---|---|
| PE | 2 | 4 mm² | 6 mm² | solid | 16 mm | 1 Nm |
| PE | 4 | 0.5 mm² | 2.5 mm² | solid | 16 mm | 1 Nm |
| N + L1 | 1 | 1.5 mm² | 4 mm² | solid | 6 mm | 0.5 Nm |
| L2 + 3 | 1 | 4 mm² | 6 mm² | solid | 6 mm | 0.5 Nm |
| D01 | 2 | 1.5 mm² | 4 mm² | solid | 12 mm | 1.2 Nm |
| Number of cable entries | Type of cable entry | Size of the metric knockouts | Position of cable entry |
|---|---|---|---|
| 10 | metric knockouts | M25, M32, M40 | wall |
Quick locking: opening and closing by quarter turn, locked position well visible (open - locked)
screw anchor
IP66IP degree of protection of the included Grommets 3x EDKF 32: IP65, sealing range 8 mm - 23 mm
IK09
Yes
Concrete C20/C25, Solid lime sandstone KSV 12, Brick MZ 12, Clinker KS 12
Indoor installation
35 °C
-25 °C up to +40 °C
≤ 50 % at 40 °C, ≤ 100 % at 25 °C
Polycarbonate
Yes
Yes
155 mm
210 mm
92 mm
1.168 kg
DIN EN 60670-1/-22, IEC 60670-1/-22, DIN 4102-12
| Type of certificate | Certificate number |
|---|---|
| AbP | P-MPA-E-25-006 |
62000448
4012591172864
1
85369010
DYNAMIC: EC002600 - Box/housing for surface mounting on the wall/ceiling
ETIM-8.0: EC002600 - Box/housing for surface mounting on the wall/ceiling
ETIM-7.0: EC002600 - Box/housing for surface mounting on the wall/ceiling
ETIM-6.0: EC002600 - Box/housing for surface mounting on the wall/ceiling
ETIM-5.0: EC002600 - Box/housing for surface mounting on the wall/ceiling
ETIM-4.0: EC002600 - Box/housing for surface mounting on the wall/ceiling
Cable junction boxes in accordance with IEC 60670-22 with permanently installed connection terminal and fused branch. Tested for functional integrity according to DIN 4102 Part 12 in conjunction with function-maintaining cables from Dätwyler and Eupen as per test certificate. Functional integrity (30 minutes, class E 30 or 90 minutes, class E 90). Fixings approved for fire protection included in the scope of delivery. Tested for insulation integrity PH120 according to BS EN 50200 in conjunction with insulation‑integrity cables; see test certificate, download at www.hensel.electric.de Type – Documents. Suitable for indoor use and protected outdoor installation according to DIN VDE 0100, Part 737. Degree of protection according to IEC 60529: IP 66 with AKMF fitting. Rated insulation voltage: 400 V. Material: thermoplastic, halogen- and silicone-free. Colour: RAL 2003, pastel orange. Cover fastening with quick-release, can be sealed without accessories. Fuse in branch: 1 x D01 base (without fuse-link). Make: HENSEL FK.
5-pole terminal, rated cross-section: 1.5-4 mm², for branching and connecting, one D01 element, dimensions H x W x D 170 x 270 x 123 mm, plus external backets.