Ui = 690 V
In = 400 A
| Maximum number of conductors clamping units each | Conductor cross-section min. | Conductor cross-section max. | Conductor cross section | Conductor type | Conductor material |
|---|---|---|---|---|---|
| 1 | 25 mm² | 240 mm² | stranded | round | Cu, Al |
| 2 | 25 mm² | 120 mm² | stranded | round | Cu, Al |
| 1 | 50 mm² | 185 mm² | solid | sector | Cu, Al |
| 2 | 50 mm² | 120 mm² | solid | sector | Cu, Al |
| 1 | 35 mm² | 240 mm² | stranded | sector | Cu |
| 2 | 35 mm² | 120 mm² | stranded | sector | Cu |
| 2 | 35 mm² | 50 mm² | solid | round | Al |
| 1 | 95 mm² | 185 mm² | stranded | sector | Al |
| 2 | 50 mm² | 95 mm² | stranded | sector | Al |
2
Screw connection
Yes
40 Nm
Yes
| Number of cable entries | Type of cable entry | Size of the metric knockouts | Position of cable entry |
|---|---|---|---|
| 4 | metric knockouts | M40, M50 | wall left+right |
| 8 | metric knockouts | M32 | wall left+right |
| 2 | metric knockouts | M20 | wall top |
| 10 | metric knockouts | M25 | wall top |
| 1 | metric knockouts | M32, M40 | wall top |
| 4 | metric knockouts | M25 | wall bottom |
| 3 | metric knockouts | M40, M50 | wall bottom |
Tool operation
IP65
IK08
Yes
Indoor installation
35 °C
-25 °C up to +40 °C
≤ 50 % at 40 °C, ≤ 100 % at 25 °C
Polycarbonate
960 °C
V-2
-25 °C up to +80 °C
Yes
Yes
600 mm
300 mm
170 mm
8.357 kg
DIN EN 60670-1/-22, IEC 60670-1/-22
3900225
4012591653073
1
85369010
DYNAMIC: EC002600 - Box/housing for surface mounting on the wall/ceiling
ETIM-8.0: EC002600 - Box/housing for surface mounting on the wall/ceiling
ETIM-7.0: EC002600 - Box/housing for surface mounting on the wall/ceiling
ETIM-6.0: EC002600 - Box/housing for surface mounting on the wall/ceiling
ETIM-5.0: EC002600 - Box/housing for surface mounting on the wall/ceiling
ETIM-4.0: EC002600 - Box/housing for surface mounting on the wall/ceiling
Cable junction boxes according to IEC 60670-22 with integral terminal block; cable entry via add-on flanges. Suitable for indoor areas and protected outdoor installation in accordance with DIN VDE 0100, Part 737. For ambient temperature maximum +40 °C and minimum -25 °C, at relative humidity 50% at +40 °C or 100% at +25 °C. Material temperature resistance from -25 °C to +90 °C; flammability behavior according to VDE 0471, Part 2 - glow-wire test 750 °C; UL 94 V-2. Degree of protection according to IEC 60529: IP 65 with add-on hubs AKM. Rated insulation voltage: 690 V. Material: thermoplastic, halogen- and silicone-free. Color: grey, RAL 7035. Lid fastening via quick-release catches, sealable without accessories. Make: HENSEL K.
Nominal cross-section: 25-240 mm², 4-pole terminal, dimensions HxWxD 600 x 300 x 170 mm