Un = 400 V
| Rated insulation voltage | Voltage type |
|---|---|
| Ui = 690 V | a.c. |
II
In = 75 A
3
No
| power dissipation capability Pde | Temperature difference |
|---|---|
| Pde = 33 W | 30 K |
| Number of clamping units per pole | Connection type |
|---|---|
| 16 | Plug-in terminal connection |
| 4 | Screw connection |
| Maximum number of conductors clamping units each | Conductor cross-section min. | Conductor cross-section max. | Conductor cross section | Conductor type | Conductor material |
|---|---|---|---|---|---|
| 1 | 1.5 mm² | 4 mm² | solid, flexible | round | Cu |
| Maximum number of conductors clamping units each | Conductor cross-section min. | Conductor cross-section max. | Conductor cross section | Conductor type | Conductor material |
|---|---|---|---|---|---|
| 4 | 1.5 mm² | 2.5 mm² | solid | round | Cu |
| 1 | 1.5 mm² | 25 mm² | flexible | round | Cu |
| 3 | 4 mm² | 6 mm² | solid | round | Cu |
| 1 | 10 mm² | 10 mm² | solid | round | Cu |
| 1 | 16 mm² | 25 mm² | stranded | round | Cu |
| Number of cable entries | Type of cable entry | Size of the metric knockouts | Position of cable entry |
|---|---|---|---|
| 8 | metric knockouts | M20 | wall top+bottom |
| 4 | metric knockouts | M20 | wall top+bottom |
| 2 | metric knockouts | M20, M25 | wall top+bottom |
| 1 | metric knockouts | M32 | wall top+bottom |
Door
Yes
18 modules
1
sealing plug, DIN rail(s), blanking strips, labelling strips, cable entry cover
IP65
Open
Indoor installation
35 °C
-5 °C up to +40 °C
≤ 50 % at 40 °C, ≤ 100 % at 25 °C
Polystyrene
750 °C
V-2
-25 °C up to +80 °C
Yes
Yes
333 mm
403 mm
129 mm
2.37 kg
EN 60670-1, DIN EN 60670-24
6100047
4012591620471
1
85381000
DYNAMIC: EC000214 - Small distribution board
ETIM-8.0: EC000214 - Small distribution board
ETIM-7.0: EC000214 - Small distribution board
ETIM-6.0: EC000214 - Small distribution board
ETIM-5.0: EC000214 - Small distribution board
ETIM-4.0: EC000214 - Small distribution board
Small-type distribution boards in accordance with DIN EN 60670-24 and IEC 61439-3, for installing devices with snap-on mounting up to 63 A in accordance with DIN 43880, with protective insulation (protection class II). PE and N terminals in FIXCONNECT push-in terminal technology with push-in terminals from 1.5 mm² to 4 mm² for solid and flexible copper conductors, and screw terminals with clamping yoke from 1.5 mm² to 25 mm² with conductor protection and protection against self-loosening for solid, stranded and flexible copper conductors. Suitable for indoor areas and protected outdoor installation in accordance with DIN VDE 0100, Part 737. For ambient temperature maximum +40 °C and minimum -5 °C, at relative humidity 50% at +40 °C or 100% at +25 °C. Material temperature resistance from -25 °C to +70 °C. Flammability in accordance with VDE 0471, Part 2 – glow-wire test 750 °C, UL Subject 94 V-2. Rated voltage 400 V. Rated current of the N busbar: I = 75 A. Material: thermoplastic, halogen- and silicone-free. Colour: grey, RAL 7035 with transparent door covering all rows. Make: HENSEL KV.
Degree of protection: IP 65 with metric knockouts. 18 modules of 18 mm each. Dimensions HxWxD 333 x 403 x 129 mm.