Un = 690 V
| Rated insulation voltage | Voltage type |
|---|---|
| Ui = 690 V | a.c. |
| Ui = 1000 V | d.c. |
withoutin orer to achieve protection class II and protection class IP 65: please order closing plate set, single closing plate sets and flanges separately.
250 A
Icw = 13 kA / 0.3 s
Ipk = 26 kA
Tool operation
connector
| Name of the pole | Width of the busbar | Thickness of the busbar | ||
|---|---|---|---|---|
| L1-L3, N, PE |
|
|
60 mm
180 mm, 288 mm
Yes
in connection with accessories
IK08
No
Indoor installation
35 °C
-5 °C up to +40 °C
≤ 50 % at 40 °C, ≤ 100 % at 25 °C
| power dissipation capability Pde | Temperature difference |
|---|---|
| Pde = 1.2 W | 1 K |
Polycarbonate
960 °C
Yes
Yes
Yes
360 mm
540 mm
163 mm
5.32 kg
transparent
grey
DIN EN IEC 61439-3
68000217
4012591104216
1
85371098
DYNAMIC: EC002274 - Busbar housing
ETIM-9.0: EC002274 - Busbar housing
ETIM-8.0: EC002274 - Busbar housing
ETIM-7.0: EC002274 - Busbar housing
ETIM-6.0: EC002274 - Busbar housing
ETIM-5.0: EC002274 - Busbar housing
ETIM-4.0: EC002274 - Busbar housing
Combinable enclosure system with door for the assembly of distribution boards up to 250 A to be opperated by ordinary persons (DBO) in accordance with IEC 61439-3 for surface-mounting. Enclosures are suitable for the outdoor installation - harsh environment and / or outdoor, however the climatic influences and effects on the equipment are to be considered. Bottom parts and doors are made from impact-resistant polycarbonate, halogen- and silicone-free, colour RAL 7035. All enclosures with doors, which are lockable and sealable. Operation of device behind the doors. Burning behavior in accordance with IEC 60695-2-11 Glow wire test + 960° C. Protective measure: protective insulation (protection class II). Make: Hensel ENYSTAR.
Busbar box 5-pole, N-conductor with the same current-carrying capacity as the outer conductors. Door lock with tool operation. Degree of protection: IP 65 according to DIN EN 60 529. Dimensions HxWxD 360 x 540 x 163 mm