Un = 690 V
| Rated insulation voltage | Voltage type |
|---|---|
| Ui = 690 V | a.c. |
| Ui = 1000 V | d.c. |
withoutin orer to achieve protection class II and protection class IP 65: please order closing plate set, single closing plate sets and flanges separately.
In = 160 A
InC = 128 Afor design verification of permissible temperature rise in accordance with IEC 61439-1, section 10.10.4
In = 192 A
| Rated ultimate short-circuit breaking capacity | Rated voltage | Voltage type |
|---|---|---|
| ICS = ICU = 8 kA | Un = 690 V | a.c. |
| ICS = ICU = 36 kA | Un = 415 V | a.c. |
112 A - 160 A
No
| Maximum number of conductors clamping units each | Conductor cross-section min. | Conductor cross-section max. | Conductor cross section | Conductor type | Conductor material |
|---|---|---|---|---|---|
| 1 | 1.5 mm² | 95 mm² | round |
| Maximum number of conductors clamping units each | Conductor cross-section min. | Conductor cross-section max. | Conductor cross section | Conductor type | Conductor material |
|---|---|---|---|---|---|
| 2 | 70 mm² | 70 mm² | stranded | Cu | |
| 4 | 25 mm² | 50 mm² | stranded | Cu | |
| 6 | 16 mm² | 16 mm² | stranded | Cu |
| Width | Depth / Thickness | Conductor material |
|---|---|---|
| 25 mm | 5 mm | Cu |
Yes
Tool operation
connector
Yes
in connection with accessories
IK08
No
Indoor installation
35 °C
-5 °C up to +40 °C
≤ 50 % at 40 °C, ≤ 100 % at 25 °C
| power dissipation capability Pde | Temperature difference |
|---|---|
| Pde = 0.6 W | 1 K |
Polycarbonate
960 °C
Yes
Yes
Yes
360 mm
270 mm
163 mm
5.555 kg
transparent
grey
DIN EN IEC 61439-3
68000224
4012591104384
1
85371098
DYNAMIC: EC002283 - Distributor assembly with power circuit-breaker
ETIM-9.0: EC002283 - Distributor assembly with power circuit-breaker
ETIM-8.0: EC002283 - Distributor assembly with power circuit-breaker
ETIM-7.0: EC002283 - Distributor assembly with power circuit-breaker
ETIM-6.0: EC002283 - Distributor assembly with power circuit-breaker
ETIM-5.0: EC002283 - Distributor assembly with power circuit-breaker
ETIM-4.0: EC002283 - Distributor assembly with power circuit-breaker
Combinable enclosure system with door for the assembly of distribution boards up to 250 A to be opperated by ordinary persons (DBO) in accordance with IEC 61439-3 for surface-mounting. Enclosures are suitable for the outdoor installation - harsh environment and / or outdoor, however the climatic influences and effects on the equipment are to be considered. Bottom parts and doors are made from impact-resistant polycarbonate, halogen- and silicone-free, colour RAL 7035. All enclosures with doors, which are lockable and sealable. Operation of device behind the doors. Burning behavior in accordance with IEC 60695-2-11 Glow wire test + 960° C. Protective measure: protective insulation (protection class II). Make: Hensel ENYSTAR.
Circuit breaker box, 3-pole, with overload and short-circuit release, with PE and N terminals. Door lock with tool operation. Degree of protection: IP 65 according to IEC 60 529. Dimensions HxWxD 360 x 270 x 163 mm