FP 5216

  • Circuit breaker box
  • 1x Circuit-breaker In = 160 A, 3-pole
Product properties
Downloads
Digital product data
Product properties

ELECTRICAL PROPERTIES

Rated voltage:

Un = 690 V

Rated insulation voltage:
Rated insulation voltageVoltage type
Ui = 690 Va.c.
Ui = 1000 Vd.c.
Protection class:

withoutin orer to achieve protection class II and protection class IP 65: please order closing plate set, single closing plate sets and flanges separately.

Rated current (of the device):

In = 160 A

Rated current of a circuit:

InC = 128 Afor design verification of permissible temperature rise in accordance with IEC 61439-1, section 10.10.4

Rated current (of the terminal):

In = 192 A

Rated ultimate short-circuit breaking capacity:
Rated ultimate short-circuit breaking capacityRated voltageVoltage type
ICS = ICU = 8 kAUn = 690 Va.c.
ICS = ICU = 36 kAUn = 415 Va.c.
Setting range overcurrent release:

112 A - 160 A

CONNECTION DATA

Ferrule required for flexible conductors:

No

Connection cross-section device (outgoing):
Maximum number of conductors clamping units eachConductor cross-section min.Conductor cross-section max.Conductor cross sectionConductor typeConductor material
11.5 mm²95 mm²round
Connection cross-section N/PE terminal to device:
Maximum number of conductors clamping units eachConductor cross-section min.Conductor cross-section max.Conductor cross sectionConductor typeConductor material
270 mm²70 mm²strandedCu
425 mm²50 mm²strandedCu
616 mm²16 mm²strandedCu
Connection flat device:
WidthDepth / ThicknessConductor material
25 mm5 mmCu
Wiring area changeable:

Yes

MECHANICAL PROPERTIES

With additional protection cover behind the lid
Type of lid fastening:

Tool operation

Delivered accessories:

connector

Can be combined:

Yes

IP degree of protection:

in connection with accessories

Impact strength:

IK08

Sealable without accessories:

No

AMBIENT CONDITIONS

Application area:

Indoor installation

Maximum ambient temperature 24 h:

35 °C

Ambient temperature:

-5 °C up to +40 °C

Relative humidity:

≤ 50 % at 40 °C, ≤ 100 % at 25 °C

Rated loading factors

Rated power dissipation in ENYGUIDE:
power dissipation capability PdeTemperature difference
Pde = 0.6 W1 K
Power dissipation of the device per pole:
Pv = 13.95 W

MATERIAL PROPERTIES

Material:

Polycarbonate

Glow wire test according to IEC 60695-2-11:

960 °C

UV resistant according to DIN EN IEC 61439-1:

Yes

Halogen-free:

Yes

Silicone-free:

Yes

DIMENSIONS

Height:

360 mm

Width:

270 mm

Depth:

163 mm

Net weight:

5.555 kg

COLOURS

Colour of the lid:

transparent

Bottom part colour:

grey

CERTIFICATES

Conforming to the standards:

DIN EN IEC 61439-3

SALES DATA

Product number:

68000224

EAN:

4012591104384

Pack unit:

1

Customs tariff number:

85371098

ETIM class:

DYNAMIC: EC002283 - Distributor assembly with power circuit-breaker
ETIM-9.0: EC002283 - Distributor assembly with power circuit-breaker
ETIM-8.0: EC002283 - Distributor assembly with power circuit-breaker
ETIM-7.0: EC002283 - Distributor assembly with power circuit-breaker
ETIM-6.0: EC002283 - Distributor assembly with power circuit-breaker
ETIM-5.0: EC002283 - Distributor assembly with power circuit-breaker
ETIM-4.0: EC002283 - Distributor assembly with power circuit-breaker

NOTE

Note on the product:
  • with connectors for connecting two boxes

TENDER TEXT

Tender text (system):

Combinable enclosure system with door for the assembly of distribution boards up to 250 A to be opperated by ordinary persons (DBO) in accordance with IEC 61439-3 for surface-mounting. Enclosures are suitable for the outdoor installation - harsh environment and / or outdoor, however the climatic influences and effects on the equipment are to be considered. Bottom parts and doors are made from impact-resistant polycarbonate, halogen- and silicone-free, colour RAL 7035. All enclosures with doors, which are lockable and sealable. Operation of device behind the doors. Burning behavior in accordance with IEC 60695-2-11 Glow wire test + 960° C. Protective measure: protective insulation (protection class II). Make: Hensel ENYSTAR.

Tender text (product):

Circuit breaker box, 3-pole, with overload and short-circuit release, with PE and N terminals. Door lock with tool operation. Degree of protection: IP 65 according to IEC 60 529. Dimensions HxWxD 360 x 270 x 163 mm

Downloads
Digital product data

Attached accessories

ACCESSORIES

We use cookies