Ui = 400 V
In = 57 A
E30
with fused branch via 1x D01-Neozed fuse element
| Maximum number of conductors clamping units each | Conductor cross-section min. | Conductor cross-section max. | Conductor cross section | Conductor type | Conductor material |
|---|---|---|---|---|---|
| 1 | 1.5 mm² | 10 mm² | solid, stranded, flexible, flexible with end ferrule | round | Cu |
2
Screw connection
No
12 mm
1.2 NmWith 2 connecting terminals, 2 branch terminals and 2 PE terminals
Quick locking: opening and closing by quarter turn, locked position well visible (open - locked)
external brackets
IP66Mounted cable entries 4x EDKF 40, sealing range 11 mm - 30 mm
IK10
Yes
Indoor installation
35 °C
-25 °C up to +40 °C
≤ 50 % at 40 °C, ≤ 100 % at 25 °C
Sheet steel, powder-coated
Yes
Yes
200 mm
200 mm
80 mm
2.65 kg
DIN EN 60670-1/-22, IEC 60670-1/-22, DIN 4102-12
6000109
4012591601098
1
85369010
DYNAMIC: EC002600 - Box/housing for surface mounting on the wall/ceiling
ETIM-8.0: EC002600 - Box/housing for surface mounting on the wall/ceiling
ETIM-7.0: EC002600 - Box/housing for surface mounting on the wall/ceiling
ETIM-6.0: EC002600 - Box/housing for surface mounting on the wall/ceiling
ETIM-5.0: EC002600 - Box/housing for surface mounting on the wall/ceiling
ETIM-4.0: EC002600 - Box/housing for surface mounting on the wall/ceiling
Cable junction and connection box with built-in terminal, 5-pole and D01 16A neozed fuse base for a branch to an operating device. The damage or destruction of the fuse-protected device in the branch may not break the intrinsic fire resistance of the common supply. Tested for intrinsic fire resistance according to DIN 4102 Part 12 together with function-retaining cables of the cable manufacturers Dätwyler and Nexans, functional integrity for 30 minutes, classification E 30, according to test certificate of manufacturers. Mounting via dowels approved for fire protection and external fixings. Suitable for indoor and protected outdoor installation according to DIN VDE 0100, part 737. Degree of protection according to IEC 60529: IP 66, with mounted grommets EDK, closed. Rated insulation voltage: 400 V a.c., Material: steel sheet, protective measure: with protective conductor, protection class I. Colour: RAL 2003, pastel orange. Make: HENSEL FK.
Nominal cross-section: connection 1.5 to 10 mm², 5-pole terminal, dimensions HxWxD 200 x 200 x 80 mm