Un = 690 V
| Rated insulation voltage | Voltage type |
|---|---|
| Ui = 690 V | a.c. |
| Ui = 1000 V | d.c. |
withoutin orer to achieve protection class II and protection class IP 65: please order closing plate set, single closing plate sets and flanges separately.
In = 125 A
InC = 100 Afor design verification of permissible temperature rise in accordance with IEC 61439-1, section 10.10.4
Icc = 25 kA
| Switching capacity (for switch disconnectors) | Utilization category | Rated voltage |
|---|---|---|
| 55 kW | AC-21 A/B | Un = 690 V |
| 55 kW | AC-23 A/B | Un = 415 V |
| Maximum number of conductors clamping units each | Conductor cross-section min. | Conductor cross-section max. | Conductor cross section | Conductor type | Conductor material |
|---|---|---|---|---|---|
| 1 | 10 mm² | 70 mm² | Cu |
| Maximum number of conductors clamping units each | Conductor cross-section min. | Conductor cross-section max. | Conductor cross section | Conductor type | Conductor material |
|---|---|---|---|---|---|
| 1 | 10 mm² | 70 mm² | Cu |
| Width | Depth / Thickness | Conductor material |
|---|---|---|
| 9 mm | 4.8 mm | Cu |
Yes
Hand closure
connector
Yes
in connection with accessories
IK08
Yes
Indoor installation
35 °C
-5 °C up to +40 °C
≤ 50 % at 40 °C, ≤ 100 % at 25 °C
| power dissipation capability Pde | Temperature difference |
|---|---|
| Pde = 0.6 W | 1 K |
Polycarbonate
960 °C
Yes
Yes
Yes
360 mm
270 mm
186 mm
4.131 kg
transparent
grey
DIN EN IEC 61439-3
68000186
4012591116769
1
85371098
DYNAMIC: EC000216 - Switch disconnector (AC)
ETIM-9.0: EC000216 - Switch disconnector (AC)
ETIM-8.0: EC000216 - Switch disconnector (AC)
ETIM-7.0: EC000216 - Switch disconnector (AC)
ETIM-6.0: EC000216 - Switch disconnector (AC)
ETIM-5.0: EC000216 - Switch disconnector (AC)
ETIM-4.0: EC000216 - Switch disconnector (AC)
Combinable enclosure system with door for the assembly of distribution boards up to 250 A to be opperated by ordinary persons (DBO) in accordance with IEC 61439-3 for surface-mounting. Enclosures are suitable for the outdoor installation - harsh environment and / or outdoor, however the climatic influences and effects on the equipment are to be considered. Bottom parts and doors are made from impact-resistant polycarbonate, halogen- and silicone-free, colour RAL 7035. All enclosures with doors, which are lockable and sealable. Operation of device behind the doors. Burning behavior in accordance with IEC 60695-2-11 Glow wire test + 960° C. Protective measure: protective insulation (protection class II). Make: Hensel ENYSTAR.
Isolator box, 4-pole, with PE terminal. Door lock with manual operation. Degree of protection: IP 65 according to IEC 60529. Dimensions HxWxD 360 x 270 x 186 mm