Ui = 690 V
| Conductor cross-section max. | Rated current |
|---|---|
| 0.5 mm² | In = 3.3 A |
| 0.75 mm² | In = 4.1 A |
| 1 mm² | In = 4.9 A |
| 1.5 mm² | In = 6.5 A |
| 2.5 mm² | In = 8.2 A |
| 4 mm² | In = 9.8 A |
| 6 mm² | In = 11.5 A |
II 3G Ex ec IIC T6 Gc
II 3D Ex tc IIIC T85 Dc
| Maximum number of conductors clamping units each | Conductor cross-section min. | Conductor cross-section max. | Conductor cross section | Conductor type | Conductor material |
|---|---|---|---|---|---|
| 1 | 0.5 mm² | 6 mm² | solid, flexible | round | Cu |
2
Screw connection
No
9 mm
0.5 Nm
14
Neutral
| Number of cable entries | Type of cable entry | Size of the metric knockouts | Sealing range of the cable entry | Position of cable entry |
|---|---|---|---|---|
| 7 | Drill marking | M20, M25, M32 | wall |
Quick locking: opening and closing by quarter turn, locked position well visible (open - locked)
external brackets
IP66
No
for high mechanical hazards (7 J impact energy)
Outdoor installation
-20 °C up to +40 °C
Polycarbonate
750 °C
HB
Yes
Yes
Yes (resistant to UV exposure due to solar radiation, ice and sea water, corrosion, temperature resistant, impact-resistant)
130 mm
130 mm
77 mm
0.369 kg
DIN EN 60670-1/-22, IEC 60670-1/-22, DIN EN IEC 60079-1, DIN EN IEC 60079-7, DIN EN 60079-31
| Type of certificate | Certificate number |
|---|---|
| VDE | 40049684 |
62000343
4012591135371
1
85369010
DYNAMIC: EC002600 - Box/housing for surface mounting on the wall/ceiling
ETIM-8.0: EC002600 - Box/housing for surface mounting on the wall/ceiling
ETIM-7.0: EC002600 - Box/housing for surface mounting on the wall/ceiling
ETIM-6.0: EC002600 - Box/housing for surface mounting on the wall/ceiling
ETIM-5.0: EC002600 - Box/housing for surface mounting on the wall/ceiling
ETIM-4.0: EC002600 - Box/housing for surface mounting on the wall/ceiling
Ex Cable junction boxes according to IEC 60670-22 with built-in terminal blocks. Suitable for use in Ex zones 2 and 22 according to IEC 60079-1, IEC 60079-7 and IEC 60079-31 in indoor areas and for unprotected installation outdoors according to DIN VDE 0100, Part 737. Ex marking for explosive gas atmospheres II 3G Ex ec IIA T6 Gc. Ex marking for explosive dust atmospheres II 3D Ex tc IIIC T85 Dc. For ambient temperature maximum +40 °C and minimum -20 °C, with relative humidity 50% at +40 °C or 100% at +25 °C. Material temperature resistance from -20 °C to +80 °C, burning behavior according to VDE 0471, Part 2 - glow wire test 750 °C, UL Subject 94 HB. Degree of protection according to IEC 60529: IP 66 with Ex screw cable gland AXM. Material: PC thermoplastic, weatherproof, free of halogens and silicone. Color: black, similar to RAL 9011. Lid attachment with quick release. Plug-in external lugs for wall mounting included. Brand: HENSEL RX.
With 14 terminal blocks 0.5 - 6 mm², rated insulation voltage 690 V. Dimensions HxWxD 130 x 130 x 77 mm