Mi 6477

  • Fuse box
  • 1x Fuse base NH2, 3-pole
  • 630 A rated current of busbar
Product properties
Downloads
Digital product data
Product properties

ELECTRICAL PROPERTIES

Rated voltage:

Un = 690 V

Rated insulation voltage:
Rated insulation voltageVoltage type
Ui = 690 Va.c.
Ui = 1000 Vd.c.
Protection class:

II

Rated current (of the device):

In = 400 A

Rated current of a circuit:

InC = 320 Afor design verification of permissible temperature rise in accordance with IEC 61439-1, section 10.10.4

Rated current of busbar:

630 A

Rated short-time withstand current:

Icw = 21 kA / 1 s

Rated peak withstand current resistance (lpk):

Ipk = 45 kA

Number of devices:

1

CONNECTION DATA

an additional enclosure is required for connecting a (supply) line to the busbar.
Connection direction outgoing cable:

bottom

Connection direction modifiable:

No

Connection type:
Connection typeConnection size
Bolt connectionM 10
Bolt connectionM 10
Connection type:
Type of cableConnection typeConnection size
incoming
Bolt connectionM 10
incoming
Bolt connectionM 10

MECHANICAL PROPERTIES

Protection against accidental contact according to DIN EN IEC 61439 fulfilled by enclosure cover
Type of lid fastening:

Tool operation

Busbar polarity:

5

Busbar dimensions:
Name of the poleWidth of the busbarThickness of the busbar
L1-L3
30 mm
10 mm
N
25 mm
10 mm
PE
12 mm
10 mm
Centreline spacing of busbars:

60 mm

Can be combined:

Yes

IP degree of protection:

IP65

Impact strength:

IK08

AMBIENT CONDITIONS

Application area:

Indoor installation

Maximum ambient temperature 24 h:

35 °C

Ambient temperature:

-5 °C up to +40 °C

Relative humidity:

≤ 50 % at 40 °C, ≤ 100 % at 25 °C

Rated loading factors

Rated power dissipation in ENYGUIDE:
power dissipation capability PdeTemperature difference
Pde = 2 W1 K
Installed power dissipation of the busbar in ENYGUIDE:
Pv = 30.69 W
Power dissipation of the device per pole:
Pv = 18.7 W

MATERIAL PROPERTIES

Material:

Polycarbonate

Glow wire test according to IEC 60695-2-11:

960 °C

UV resistant according to DIN EN IEC 61439-1:

Yes

Halogen-free:

Yes

Silicone-free:

Yes

DIMENSIONS

Height:

600 mm

Width:

300 mm

Depth:

214 mm

Net weight:

10.366 kg

COLOURS

Colour of the lid:

transparent

Bottom part colour:

grey

CERTIFICATES

Conforming to the standards:

DIN EN IEC 61439-2

SALES DATA

Product number:

2000782

EAN:

4012591657828

Pack unit:

1

Customs tariff number:

85371098

ETIM class:

DYNAMIC: EC000100 - Fuse enclosure
ETIM-9.0: EC000100 - Fuse enclosure
ETIM-8.0: EC000100 - Fuse enclosure
ETIM-7.0: EC000100 - Fuse enclosure
ETIM-6.0: EC000100 - Fuse enclosure
ETIM-5.0: EC000100 - Fuse enclosure
ETIM-4.0: EC000100 - Fuse enclosure

TENDER TEXT

Tender text (system):

Insulation-enclosed power distribution board as power switchgear and controlgear assembly (PSC) in accordance with IEC 61439-2 for wall mounting. The enclosures must be suitable for outdoor installation - harsh environment and/or outdoor installation - the climatic effects on the equipment must be considered. Bottom parts and lids of the boxes made from impact-resistant polycarbonate, halogen and silicone-free, colour RAL 7035, transparent lid with quick action fasteners for tool operation. Burning behaviour according to IEC 60695-2-11 glow wire test + 960°C. Maximum water absorption 10 mg in accordance with DIN 53473. Protective measure: totally insulated (protection class II), Make: HENSEL Mi Power distribution board.

Tender text (product):

HRC fuse box NH 2, 3-pole, adapted to 5-pole busbars. Degree of protection: IP 65 according to IEC 60 529. Dimensions HxWxD 600 x 300 x 214 mm

Downloads
Digital product data

ACCESSORIES

We use cookies