Un = 690 V
| Rated insulation voltage | Voltage type |
|---|---|
| Ui = 690 V | a.c. |
| Ui = 1000 V | d.c. |
II
In = 160 A
InC = 128 Afor design verification of permissible temperature rise in accordance with IEC 61439-1, section 10.10.4
Icc = 50 kA
In = 192 A
1
Screw connection
No
| Maximum number of conductors clamping units each | Conductor cross-section min. | Conductor cross-section max. | Conductor cross section | Conductor type | Conductor material |
|---|---|---|---|---|---|
| 1 | 1.5 mm² | 70 mm² | stranded, flexible | round | Cu |
| Maximum number of conductors clamping units each | Conductor cross-section min. | Conductor cross-section max. | Conductor cross section | Conductor type | Conductor material |
|---|---|---|---|---|---|
| 2 | 70 mm² | 70 mm² | stranded | Cu | |
| 4 | 25 mm² | 50 mm² | stranded | Cu | |
| 6 | 16 mm² | 16 mm² | stranded | Cu |
| Width | Depth / Thickness | Conductor material |
|---|---|---|
| 12 mm | 10 mm | Cu |
above or below
| Connection type | Connection size |
|---|---|
| Clamp terminal | |
Tool operation
Yes
IP65
IK08
Indoor installation
35 °C
-5 °C up to +40 °C
≤ 50 % at 40 °C, ≤ 100 % at 25 °C
| power dissipation capability Pde | Temperature difference |
|---|---|
| Pde = 0.6 W | 1 K |
Polycarbonate
960 °C
Yes
Yes
Yes
300 mm
150 mm
170 mm
2.822 kg
transparent
grey
DIN EN IEC 61439-2
2000154
4012591651543
1
85371098
DYNAMIC: EC000100 - Fuse enclosure
ETIM-8.0: EC000100 - Fuse enclosure
ETIM-7.0: EC000100 - Fuse enclosure
ETIM-6.0: EC000100 - Fuse enclosure
ETIM-5.0: EC000100 - Fuse enclosure
ETIM-4.0: EC000100 - Fuse enclosure
Insulating material-encapsulated low-voltage switchgear assembly in box shape according to IEC 61439-2 for wall installation. Enclosures must be suitable for outdoor installation, and the climatic effects on the equipment must be taken into account. Box bottoms and covers made of impact-resistant polycarbonate, halogen-free and silicone-free, colour RAL 7035, transparent cover with quick fasteners for tool operation. Flammability according to IEC 60695-2-11 glow wire test +960°C. Maximum water absorption of 10 mg according to DIN 53473. Safety measure: protective insulated (protection class II). Brand: HENSEL Mi-Distributor.
HRC fuse box NH 00, 3-pole, with PE and N terminals. Degree of protection: IP 65 according to IEC 60 529. Dimensions HxWxD 300 x 150 x 170 mm