Un = 400 V
| Rated insulation voltage | Voltage type |
|---|---|
| Ui = 690 V | a.c. |
II
In = 75 A
4
No
| power dissipation capability Pde | Temperature difference |
|---|---|
| Pde = 43 W | 30 K |
| Number of clamping units per pole | Connection type |
|---|---|
| 24 | Plug-in terminal connection |
| 6 | Screw connection |
| Maximum number of conductors clamping units each | Conductor cross-section min. | Conductor cross-section max. | Conductor cross section | Conductor type | Conductor material |
|---|---|---|---|---|---|
| 1 | 1.5 mm² | 4 mm² | solid, flexible | round | Cu |
| Maximum number of conductors clamping units each | Conductor cross-section min. | Conductor cross-section max. | Conductor cross section | Conductor type | Conductor material |
|---|---|---|---|---|---|
| 4 | 1.5 mm² | 2.5 mm² | solid | round | Cu |
| 1 | 1.5 mm² | 25 mm² | flexible | round | Cu |
| 3 | 4 mm² | 6 mm² | solid | round | Cu |
| 1 | 10 mm² | 10 mm² | solid | round | Cu |
| 1 | 16 mm² | 25 mm² | stranded | round | Cu |
| Number of cable entries | Type of cable entry | Size of the metric knockouts | Position of cable entry |
|---|---|---|---|
| 4 | metric knockouts | M20 | wall top+bottom |
| 2 | metric knockouts | M20, M25 | wall top+bottom |
| 1 | metric knockouts | M32 | wall top+bottom |
Door
Yes
12 modules
4
sealing plug, DIN rail(s), blanking strips, labelling strips, cable entry cover
IP54
125 mm
Open
Indoor installation
35 °C
-5 °C up to +40 °C
≤ 50 % at 40 °C, ≤ 100 % at 25 °C
Polystyrene
750 °C
V-2
-25 °C up to +80 °C
Yes
Yes
708 mm
295 mm
129 mm
3.92 kg
EN 60670-1, DIN EN 60670-24
61000690
4012591625933
1
85381000
DYNAMIC: EC000214 - Small distribution board
ETIM-8.0: EC000214 - Small distribution board
ETIM-7.0: EC000214 - Small distribution board
ETIM-6.0: EC000214 - Small distribution board
ETIM-5.0: EC000214 - Small distribution board
ETIM-4.0: EC000214 - Small distribution board
Installation distribution board according to DIN EN 60670-24, DIN 43871 and IEC 61439-3, for installation of snap-in devices up to 63 A according to DIN 43880, double insulated (class II). PE and N terminals in FIXCONNECT push-in terminal technology with push-in terminal from 1.5 mm² to 4 mm² for solid and flexible copper conductors, as well as tension clamp terminal from 1.5 mm² to 25 mm² with wire protection and self-release protection for solid, stranded and flexible copper conductors. Suitable for indoor use and protected outdoor installation according to DIN VDE 0100, Part 737. For ambient temperature max. +40°C and min. -5°C, with relative humidity 50% at 40°C or 100% at 25°C. Material temperature resistance from -25°C to 70°C. Flammability according to VDE 0471, part 2 – glow wire test 750°C, UL Subject 94 V-2. Rated voltage: AC 400 V. Rated current of the N-busbar: I = 75 A. Material: thermoplastic, halogen- and silicone-free. Color: grey, RAL 7035 with transparent door across all mounting rows. Manufacturer: HENSEL KV.
Degree of protection: IP 54 with metric knockouts. 48 modules per 18 mm. Dimensions HxWxD 708 x 295 x 129 mm.