Un = 400 V
| Rated insulation voltage | Voltage type |
|---|---|
| Ui = 690 V | a.c. |
II
In = 75 A
4
No
| power dissipation capability Pde | Temperature difference |
|---|---|
| Pde = 38 W | 30 K |
| Number of clamping units per pole | Connection type |
|---|---|
| 32 | Plug-in terminal connection |
| 8 | Screw connection |
| Maximum number of conductors clamping units each | Conductor cross-section min. | Conductor cross-section max. | Conductor cross section | Conductor type | Conductor material |
|---|---|---|---|---|---|
| 1 | 1.5 mm² | 4 mm² | solid, flexible | round | Cu |
| Maximum number of conductors clamping units each | Conductor cross-section min. | Conductor cross-section max. | Conductor cross section | Conductor type | Conductor material |
|---|---|---|---|---|---|
| 4 | 1.5 mm² | 2.5 mm² | solid | round | Cu |
| 1 | 1.5 mm² | 25 mm² | flexible | round | Cu |
| 3 | 4 mm² | 6 mm² | solid | round | Cu |
| 1 | 10 mm² | 10 mm² | solid | round | Cu |
| 1 | 16 mm² | 25 mm² | stranded | round | Cu |
| Number of cable entries | Type of cable entry | Size of the metric knockouts | Sealing range of the cable entry | Position of cable entry |
|---|---|---|---|---|
| 8 | metric knockouts | M20 | wall top+bottom | |
| 8 | Conduit entry | M16, M20 | wall top+bottom | |
| 1 | Conduit entry | M25, M32 | wall top+bottom | |
| 6 | elastic membranes | without | 9 mm - 18 mm | wall top+bottom |
Door
Yes
18 modules
2
sealing plug, DIN rail(s), blanking strips, labelling strips, cable entry cover
IP54
150 mm
Open
Indoor installation
35 °C
-5 °C up to +40 °C
≤ 50 % at 40 °C, ≤ 100 % at 25 °C
Polystyrene
750 °C
V-2
-25 °C up to +80 °C
Yes
Yes
483 mm
403 mm
129 mm
3.23 kg
EN 60670-1, DIN EN 60670-24
61001011
4012591107606
1
85381000
DYNAMIC: EC000214 - Small distribution board
ETIM-8.0: EC000214 - Small distribution board
ETIM-7.0: EC000214 - Small distribution board
ETIM-6.0: EC000214 - Small distribution board
ETIM-5.0: EC000214 - Small distribution board
ETIM-4.0: EC000214 - Small distribution board
Small-type distribution board in accordance with DIN EN 60670-24 and IEC 61439-3, for the installation of devices with snap-on mounting up to 63 A according to DIN 43880, protectively insulated (protection class II). PE and N terminals in FIXCONNECT plug-in terminal technology with push-in terminal from 1.5 mm² to 4 mm² for solid and flexible copper conductors, as well as clamping yoke terminal from 1.5 mm² to 25 mm² with wire protection and protection against self-loosening for solid, stranded and flexible copper conductors. Suitable for indoor areas and protected outdoor installation in accordance with DIN VDE 0100, Part 737. For ambient temperature maximum +40 °C and minimum -5 °C, at relative humidity 50% at +40 °C or 100% at +25 °C. Material temperature resistance from -25 °C to +70 °C. Flammability according to VDE 0471, Part 2 – glow-wire test 750 °C, UL Subject 94 V-2. Rated voltage 400 V. Rated current of the neutral bar: I = 75 A. Material: thermoplastic, halogen- and silicone-free. Color: grey, RAL 7035, with transparent door across all installation rows. Manufacturer: HENSEL KV.
Degree of protection: IP 54 with integrated, elastic membranes. 36 modules per 18 mm. Dimensions HxWxD 483 x 403 x 129 mm.