Un = 415 V
| Rated insulation voltage | Voltage type |
|---|---|
| Ui = 690 V | a.c. |
| Ui = 1000 V | d.c. |
II
In = 63 A
InC = 50.4 Afor design verification of permissible temperature rise in accordance with IEC 61439-1, section 10.10.4
Icc = 50 kA
1
| Switching capacity (for switch disconnectors) | Utilization category | Rated voltage |
|---|---|---|
| 30 kW | AC-23 A/B | Un = 415 V |
No
| Maximum number of conductors clamping units each | Conductor cross-section min. | Conductor cross-section max. | Conductor cross section | Conductor type | Conductor material |
|---|---|---|---|---|---|
| 1 | 2.5 mm² | 35 mm² | Cu |
| Maximum number of conductors clamping units each | Conductor cross-section min. | Conductor cross-section max. | Conductor cross section | Conductor type | Conductor material |
|---|---|---|---|---|---|
| 1 | 2.5 mm² | 50 mm² | stranded | Cu | |
| 1 | 2.5 mm² | 35 mm² | flexible, flexible with end ferrule | Cu |
bottom
top
Yes
Tool operation
Yes
IP65
IK08
Indoor installation
35 °C
-5 °C up to +40 °C
≤ 50 % at 40 °C, ≤ 100 % at 25 °C
| power dissipation capability Pde | Temperature difference |
|---|---|
| Pde = 1.2 W | 1 K |
Polycarbonate
960 °C
Yes
Yes
Yes
300 mm
300 mm
239 mm
transparent
grey
DIN EN IEC 61439-2
20001580
4012591183396
1
85371098
DYNAMIC: EC000216 - Switch disconnector (AC)
ETIM-9.0: EC000216 - Switch disconnector (AC)
ETIM-8.0: EC000216 - Switch disconnector (AC)
ETIM-7.0: EC000216 - Switch disconnector (AC)
ETIM-6.0: EC000216 - Switch disconnector (AC)
ETIM-5.0: EC000216 - Switch disconnector (AC)
ETIM-4.0: EC000216 - Switch disconnector (AC)
Insulating material-encapsulated low voltage switchgear combination in box design according to IEC 61439-2 for wall mounting. Housings must be suitable for outdoor installation; climatic influences and impacts on the equipment must be considered. Housing bases and covers made of impact-resistant polycarbonate, halogen and silicone free. Colour RAL 7035, cover transparent with quick-release fasteners for tool operation. Fire behaviour according to IEC 60695-2-11 glow-wire test + 960°C. Maximum water absorption 10 mg according to DIN 53473. Protective measure: protective insulation (protection class II). Manufacturer: HENSEL Mi-Distributor.
changeover switch box 63 A, 4-pole, with PE terminal. Degree of protection: IP 65 according to IEC 60529. Dimensions HxWxD 300 x 600 x 324 mm