Ui = 690 V
In = 20 A
| Maximum number of conductors clamping units each | Conductor cross-section min. | Conductor cross-section max. | Conductor cross section | Conductor type | Conductor material |
|---|---|---|---|---|---|
| 4 | 0.75 mm² | 1 mm² | solid, stranded, flexible | round | Cu |
| 3 | 1.5 mm² | 1.5 mm² | solid, stranded, flexible | round | Cu |
| 2 | 2.5 mm² | 2.5 mm² | solid, stranded, flexible | round | Cu |
| 1 | 4 mm² | 4 mm² | solid, stranded, flexible | round | Cu |
2
Screw connection
No
10 mm
0.5 Nm
| Number of cable entries | Type of cable entry | Size of the metric knockouts | Sealing range of the cable entry | Position of cable entry |
|---|---|---|---|---|
| 7 | elastic membranes | M20 | 6 mm - 15 mm | wall |
| 1 | elastic membranes | without | 6 mm - 13 mm | bottom |
Quick locking: opening and closing by quarter turn, locked position well visible (open - locked)
external brackets, retaining strap, sealing plug
IP66
IK07
Yes
Indoor installation
35 °C
-25 °C up to +40 °C
≤ 50 % at 40 °C, ≤ 100 % at 25 °C
Polypropylene
750 °C
V-2
-25 °C up to +80 °C
Yes
Yes
93 mm
93 mm
62 mm
0.129 kg
DIN EN 60670-1/-22, IEC 60670-1/-22
| Type of certificate | Certificate number |
|---|---|
| VDE | 40049684 |
62000001
4012591124931
5
85369010
DYNAMIC: EC002600 - Box/housing for surface mounting on the wall/ceiling
ETIM-8.0: EC002600 - Box/housing for surface mounting on the wall/ceiling
ETIM-7.0: EC002600 - Box/housing for surface mounting on the wall/ceiling
ETIM-6.0: EC002600 - Box/housing for surface mounting on the wall/ceiling
ETIM-5.0: EC002600 - Box/housing for surface mounting on the wall/ceiling
ETIM-4.0: EC002600 - Box/housing for surface mounting on the wall/ceiling
Cable junction boxes according to IEC 60670-22 with built-in connecting terminal and breakout, elastic membranes. Suitable for indoor areas and protected outdoor installation according to DIN VDE 0100, Part 737. For ambient temperature max. +40°C and min. -25°C, with relative humidity 50% at +40°C or 100% at +25°C. Material temperature resistance from -25°C to +70°C, flammability according to VDE 0471, Part 2 - glow wire test 750°C, UL Subject 94 V-2. Degree of protection according to IEC 60529: IP 66. Rated insulation voltage: 690 V. Material: thermoplastic, halogen-free and silicone-free. Colour: grey, RAL 7035. Cover fastening with quick release, can be sealed without accessories. Plug-in external brackets for wall mounting included. Brand: HENSEL ENYCASE DK.
Nominal cross-section: 0.75-2.5 mm², 5-pole terminal block, dimensions HxWxD 93 x 93 x 62 mm