Un = 500 V
| Rated insulation voltage | Voltage type |
|---|---|
| Ui = 690 V | a.c. |
| Ui = 1000 V | d.c. |
II
In = 63 A
InC = 50.4 Afor design verification of permissible temperature rise in accordance with IEC 61439-1, section 10.10.4
630 A
Icw = 21 kA / 1 s
Ipk = 45 kA
6
E 33
Gauge ring
| Maximum number of conductors clamping units each | Conductor cross-section min. | Conductor cross-section max. | Conductor cross section | Conductor type | Conductor material |
|---|---|---|---|---|---|
| 1 | 16 mm² | 70 mm² | stranded, flexible | round | Cu |
| Maximum number of conductors clamping units each | Conductor cross-section min. | Conductor cross-section max. | Conductor cross section | Conductor type | Conductor material |
|---|---|---|---|---|---|
| 1 | 1.5 mm² | 35 mm² | flexible | round | Cu |
| 1 | 1.5 mm² | 10 mm² | solid | round | Cu |
| Maximum number of conductors clamping units each | Conductor cross-section min. | Conductor cross-section max. | Conductor cross section | Conductor type | Conductor material |
|---|---|---|---|---|---|
| 1 | 1.5 mm² | 16 mm² | solid, stranded, flexible | round | Cu |
| Width | Depth / Thickness | Conductor material |
|---|---|---|
| 9 mm | 6 mm | Cu |
Hand closure
5
| Name of the pole | Width of the busbar | Thickness of the busbar | ||
|---|---|---|---|---|
| L1-L3 |
|
| ||
| N |
|
| ||
| PE |
|
|
60 mm
Yes
IP65
IK08
Indoor installation
35 °C
-5 °C up to +40 °C
≤ 50 % at 40 °C, ≤ 100 % at 25 °C
| power dissipation capability Pde | Temperature difference |
|---|---|
| Pde = 1.9 W | 1 K |
Polycarbonate
960 °C
Yes
Yes
Yes
300 mm
600 mm
170 mm
13.286 kg
transparent
grey
DIN EN IEC 61439-2
2000718
4012591657187
1
85371098
DYNAMIC: EC000100 - Fuse enclosure
ETIM-9.0: EC000100 - Fuse enclosure
ETIM-8.0: EC000100 - Fuse enclosure
ETIM-7.0: EC000100 - Fuse enclosure
ETIM-6.0: EC000100 - Fuse enclosure
ETIM-5.0: EC000100 - Fuse enclosure
ETIM-4.0: EC000100 - Fuse enclosure
Insulation-enclosed power distribution board as power switchgear and controlgear assembly (PSC) in accordance with IEC 61439-2 for wall mounting. The enclosures must be suitable for outdoor installation - harsh environment and/or outdoor installation - the climatic effects on the equipment must be considered. Bottom parts and lids of the boxes made from impact-resistant polycarbonate, halogen and silicone-free, colour RAL 7035, transparent lid with quick action fasteners for tool operation. Burning behaviour according to IEC 60695-2-11 glow wire test + 960°C. Maximum water absorption 10 mg in accordance with DIN 53473. Protective measure: totally insulated (protection class II), Make: HENSEL Mi Power distribution board.
Fuse box with screw-type fuse D III, 63 A, 3-pole, adapted to 5-pole busbars. Degree of protection: IP 65 according to IEC 60 529. Dimensions HxWxD 300 x 600 x 170 mm