Tender text:
Small-type distribution board according to EN 60670-24 and IEC 61439 -3, for the installation of DIN rail equipment up to 63 A in accordance with DIN 43880, total insulated (protection class II). FIXCONNECT terminal technology for PE and N terminals from 1.5 mm² to 4 mm² for solid and flexible copper conductors as well as a terminal from 1.5 mm² to 25 mm² with wire protection and protection against self-loosening for solid, stranded and flexible copper conductors. Suitable for indoor installations - normal environment and/or protected outdoor installations - according to DIN VDE 0100, part 737. For ambient temperatures of maximum + 40°C and minimum - 5°C, relative humidity 50% at 40°C or 100% at 25°C, material temperature resistance from - 40°C to 70°C burning behaviour according to IEC 60695-2-11 - glow wire test 750°C, UL Subject 94 V-2. Rated voltage: AC 230/400 V. Rated current of the N-bar: I= 75 A. Material: thermoplastic, halogen and silicon-free. Colour: grey, RAL 7035 with transparent lid. Make: HENSEL KV, Degree of protection: IP 54 with integrated, elastic membranes 9 modules, 18 mm each. Dimensions HxWxD 238 x 200 x 111 mm